Differential Pressure Transmitter 982R from 0 to 1000 mbar

The differential pressure transmitters of the 982R series are used to measure differential pressure, overpressure and vacuum. They provide one adjustable pressure range and one output signal. Monitoring of gaseous, non-combustible and non-aggressive media.
The end of the pressure range can be reduced to 50% of its factory set full scale value simply by the use of a push-button.
Applications
- Building automation, air conditioning systems and clean room monitoring
- Valve and flap control
- Filter, ventilator and blower monitoring
- Control of air flows
Technical data
- Setting ranges:
Type Pressure ranges between Overload capacity 982R.623 0 and 100 Pa 60 kPa 982R.633 0 and 250 Pa 60 kPa 982R.643 0 and 500 Pa 75 kPa 982R.653 0 and 1 kPa 75 kPa 982R.663 0 and 2,5 kPa 85 kPa 982R.673 0 and 5 kPa 85 kPa 982R.683 0 and 10 kPa 85 kPa 982R.693 0 and 25 kPa 135 kPa 982R.6A3 0 and 50 kPa 200 kPa 982R.6B3 0 and 100 kPa 200 kPa - Temperature range:
Working and Storage temperature from –20°C to +70°C - Process connection:
6,0 mm hose connection - Supply voltage:
3-wire type:
18 to 30 VAC / VDC
2-wire type:
18 to 30 VDC - Output signal:
- 3-wire type:
- 0 – 10 VDC or
4 – 20 mA
2-wire type:
4 – 20 mA - Electrical connection:
Spring terminals for wires and leads up to 1.5 mm2 or circular connectors M12 / 4-pole - Protection class:
IP54 with protection cover acc. to EN 60529